Power-factor correction
Steady balanced load.
Method
Qc = P (tan φ1 − tan φ2). Worked case: 18.85 kW from 0.85 to 0.95 needs about 5.49 kVAr.
Logic: how this figure is built.
Last checked 2 October 2026. See the common-calculations note and the disclaimer.